Cyclopedia of heating, plumbing and sanitation; a complete reference work . heaters in Table XXXI may be changed to linear feet of 1 inch pipeby multiplying the numbers in column three (sauare feet of surface)by three. 190 HEATING AND VENTILATION 181 EXAMPLES FOR PRACTICE 1. A machine shop 100 feet long by 50 feel wide and having 3stories, each 10 feet high, is to be warmed by forced blast, Fig. 158. Illustrating Application of Forced Hlast for Warming a Factory,exhaust steam in the heater. The air is to be returned to the heaterfrom the building, and the whole amount contained in the
Cyclopedia of heating, plumbing and sanitation; a complete reference work . heaters in Table XXXI may be changed to linear feet of 1 inch pipeby multiplying the numbers in column three (sauare feet of surface)by three. 190 HEATING AND VENTILATION 181 EXAMPLES FOR PRACTICE 1. A machine shop 100 feet long by 50 feel wide and having 3stories, each 10 feet high, is to be warmed by forced blast, Fig. 158. Illustrating Application of Forced Hlast for Warming a Factory,exhaust steam in the heater. The air is to be returned to the heaterfrom the building, and the whole amount contained in the buildingis to pass through the heater every 15 minutes. What size of blower 191 182 HEATIXC AXD VKXTILATION will be required, and whal will be the II. 1*. of tin* engine required to run it? How many linear fed of 1-inch pipe should the heater eon-tain? 1-foot \s. { 0 H. P. engine. 1,071 feet of pipe.